A pressure or air test tells you a new sewer does not leak. It does not tell you whether the pipe is laid to grade, whether a joint has been pushed off line, or whether a lump of concrete is sitting in the invert. That is what a CCTV inspection is for, and on most new sewer projects it is one of the last steps before the asset is handed over.
Here is what a handover CCTV inspection involves, what it is looking for, and how to make sure the footage and report are accepted first time.
What CCTV inspection is
CCTV inspection of pipelines sends a remote camera through the pipe between maintenance holes, recording continuous footage and the distance travelled. The operator notes every joint, connection and defect as the camera moves, so each observation can be located later without digging. See what is CCTV pipe inspection and can existing pipes be inspected without excavation.
Why authorities ask for it on new sewers
For an asset owner, CCTV footage is the baseline record of the pipe they are taking over. It shows that the line was built as designed and gives them something to compare against in years to come. Many authorities require inspections to be coded and reported in a consistent way, commonly using the Conduit Inspection Reporting Code (WSA 05), so that every defect is described the same way regardless of who carried out the survey.
What the camera is looking for
- Joints: displaced, open or deflected joints, and rubber rings showing in the pipe.
- Shape: signs the pipe has deformed under backfill, which is then confirmed by deflection testing.
- Grade: ponding water that suggests sags in the line.
- Debris: soil, stones, concrete or construction waste left in the pipe.
- Connections: junctions at the right position and in the right orientation, with nothing protruding into the main.
- Damage: cracks, chips or holes from handling, installation or later works.
Where CCTV fits in the testing sequence
CCTV is normally carried out once backfill and compaction are complete and the line has passed its air or vacuum test, so the footage shows the pipe as it will be handed over. Maintenance holes are usually checked separately with vacuum testing of structures. If the inspection finds a problem, the section is repaired, and both the test and the CCTV may need to be repeated. Our guide to deflection and compaction testing explains why the order matters.
Getting the inspection accepted first time
- Flush and clean the line beforehand; debris and water hide defects and can make the footage unusable.
- Make sure maintenance hole numbers on site match the drawings, so the report lines up with the as-built plans.
- Check the authority’s reporting requirements (format, coding standard and file delivery) before the survey.
- Keep the CCTV report with the pressure, vacuum and deflection results for the handover package.
For more on reporting, see what information is included in a test report and can reports assist with asset handover.